HomeMy WebLinkAbout12052024 BSC Agenda Item 4 HVAC LOCATION Editor's note: Section 18-68 is a currently reserved section within Chapter 18(Buildings and Development)and under Article II (General Regulations).The intent of this code addition is to establish general rules and regulations for the installation of generators.The Zoning& Planning Commission is currently considering zoning amendments that would revise permitted projections for generators into required yard or setback areas. Sec. 18-68. Generators. (1) Location. All generators shall be installed in compliance with the minimum setback standards outlined in Table 7A-2:Yards(or`setbacks').See also Table 7A-7(Projections Schedule)for authorized projections into required yard or setback areas. (2) Clearance. All generators shall be installed with a minimum clearance of eighteen (18)inches from any structure or shall be installed as per the manufacturers specifications for minimum clearance for the specific model of generator to be installed,the more restrictive thereof. (3) Building Codes. All mechanical equipment shall meet all other applicable requirements of the International Building and Residential Codes adopted by the city. Created: 2024-07-14 13:49:32 [EST] (Supp. No.45) Page 1 of 1