HomeMy WebLinkAboutORD 1946 Amending Appendix C of the Code relating to Basement ConstructionCity of West University Place
Harris County, Texas
ORDINANCE NO. 1946
AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF WEST
UNIVERSITY PLACE, TEXAS AMENDING APPENDIX C - TECHNICAL
CODES, OF THE CODE OF ORDINANCES OF THE CITY OF WEST
UNIVERSITY PLACE, TEXAS, BY ADDING A NEW SUBSECTION C-
104, 11., RELATING TO BASEMENT CONSTRUCTION AND
CONTAINING FINDINGS AND PROVISIONS RELATING TO THE
SUBJECT.
NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY
OF WEST UNIVERSITY PLACE, TEXAS, THAT:
Section 1. Appendix C - Technical Codes, of the Code of Ordinances of the
City of West University Place, Texas is amended by the adoption of a new Subsection
C-104, 11., relating to basement construction. All other portions of Appendix C -
Technical Codes, of the Code of Ordinances not specifically amended hereby remain in
full force and effect.
Section 2. All ordinances and parts of ordinances in conflict with this
Ordinance are repealed to the extent of the conflict only.
Section 3. If any word, phrase, clause, sentence, paragraph, section or other
part of this Ordinance or the application thereof to any person or circumstance, shall
ever be held to be invalid or unconstitutional by any court of competent jurisdiction,
neither the remainder of this Ordinance, nor the application of such word, phrase,
clause, sentence, paragraph, section or other part of this Ordinance to any other
persons or circumstances, shall be affected thereby.
Section 4. The City Council officially finds, determines and declares that a
sufficient written notice of the date, hour, place and subject of each meeting at which
this Ordinance was discussed, considered or acted upon was given in the manner
required by the Texas Open Meetings Act, as amended, and that each such meeting
has been open to the public as required by law at all times during such discussion,
consideration and action. The City Council ratifies, approves and confirms such notices
and the contents and posting thereof.
Section 5. This Ordinance takes effect immediately upon its passage and
adoption on second reading.
PASSED, APPROVED. AND ADOPTED ON FIRST READING on the 8th day
of August J2011.
00082540
1
PASSED, APPROVED AND ADOPTED ON SECOND READING, AND
NED, on the 22"d day of August 2011.
~~~q !lNryF~~,A
eal) ~
•e
y, r
r3 +~w
r st• Signed:
The ma Lenz, City Secretary Bob Fry, Mayo
Recommended:
Michael Ros, City Manager
Approved as to legal form: -
Alan Petrov, City Attorney
00082540
Section C-104
11. All basement construction for each new building (and each new basement for an
existing building) shall meet the requirements of this section.
a. Definitions.
"A2LA Lab", "RLPE" and "RLGE" have the same meaning as stated in section
3.a. of this Section C-104 above.
b. Soil Testing and Design. Soil testing and designs shall meet all the criteria
set out in this Section C-104, as well as the following additional mandatory
requirements:
(1) The minimum depth for test boring holes shall be 30 feet.
(2) The RLPE shall certify that the plans and specifications were designed
using a 1 inch potential vertical rise. Potential vertical rise (PVR) to be
determined in accordance with Test Method Tex-124-E, Rev. January
1, 1978/December 1982, Texas State Department of Highways and
Public Transportation, Materials and Test Division, "Method for
Determining the Potential Vertical Rise, PVR" (a copy of which is on
file in the office of the City Secretary). For this purpose, the "dry"
moisture condition (from which little shrinkage is experienced, but
where volumetric swell potential is greatest) shall be used for each
sample and test.
(3) The RLPE shall certify that the plans and specifications were designed
assuming water level rises to ground level for all hydrostatic and uplift
pressure designs.
c. Foundation, Basement Walls and Floors. Foundations shall meet all the
criteria set out in this Section C-104, as well as the following additional
mandatory requirements:
(1) The entire foundation of the building and the walls and floor of the
basement shall be cast-in-place concrete.
(2) Shoring shall be required during any and all excavation. All shoring
shall be designed based on the recommendations of the RLGE and
approved by the RLPE.
(3) All foundation walls shall be designed to resist the earth pressures at-
rest and to resist full hydrostatic loading to ground surface. If the soil
tests indicate the presence of expansive soils, the walls shall be
designed to resist lateral swelling pressures also.
(4) Minimum wall and floor thickness shall be: Wall = 8 inches, Floor = 8
inches.
(5) Minimum reinforcement of all concrete shall be two layers of #4 grade
60 rebar 16 inches on center each way.
(6) Minimum concrete testing shall consist of testing each truck with 7 and
28 day test breaks with an approval letter from the RLPE delivered to
00082540
3
the office of the building official and acknowledged by the same prior to
continuing any further construction.
(7) Minimum concrete strength shall be 3000 PSI at 28 days.
(8) Monolithic concrete placement is mandatory for all walls, wall to wall
connections and in floors. Wall to floor connections maybe monolithic
or segmented.
d. Drainage. Foundation drainage plans, outside and inside of a basement,
shall include the following minimum requirements:
(1) Drains shall be provided around all concrete foundations that retain
earth and enclose habitable or usable spaces located below grade.
Gravel or crushed stone drains, perforated pipe or other approved
systems or materials shall be installed at or below the area to be
protected and shall discharge by gravity or mechanical means into an
approved drainage system. Gravel or crushed stone drains shall
extend at least 1 foot (305 mm) beyond the outside edge of the footing
and 6 inches (152 mm) above the top of the footing and be covered
with a commercial grade filter cloth Type A woven or non-woven, non-
bio degradable plastic yarn meeting at a minimum all of the following
ASTM Standards: Grab tensile strength (ASTM D 1682 @ 90 lbs. min.;
Burst strength (ASTM D 751) @ 100 psi min.; Equivalent opening size
(OES) @ 40 min., 100 Max. Perforated pipe shall be covered with the
above filter membrane material and placed on a minimum of 2 inches
(51 mm) of washed gravel or crushed rock at least one sieve size
larger than the pipe opening or perforation and covered with not less
than 6 inches (152 mm) of the same material. There must be a
granular drainage layer beneath the floor slab.
(2) Separate sump pumps for outside and inside the basement which shall
be a minimum of 1/4-horsepower sump pumps. The sump pumps shall
be rated at four times the estimated seepage rate and shall discharge
away from the building to the public storm sewer system. The drainage
systems shall be provided with a positive means of preventing
backflow. Pumps shall be accessible for removal and maintenance.
(3) Emergency power supply for sump pumps shall be provided. Natural
Gas or LP Gas (10 gallon storage maximum) systems allowed, no
battery systems shall be allowed. Systems shall be located outside, not
in basement area.
e. Waterproofing. Waterproofing shall include the following minimum
requirements:
(1) The entire exterior basement walls shall be covered with waterproofing
materials designed for below grade/soil contact that will withstand the
stated hydraulic pressures per the soil report.
(2) The exterior wall waterproofing shall be protected with a protection
board of extruded polystyrene or equal non-bio degradable product.
00082540
4
f. Mechanical, Electrical or Plumbing. Mechanical, electrical or plumbing
equipment shall meet all the requirements set out in Section 18-67 of the
City's Buildings and Development ordinances as well as the following
additional requirements:
(1) Minimum height above finished floor of the basement for the base of
any such equipment shall be eighteen (18) inches.
(2) Gas fired appliances shall not be allowed inside any basement.
(3) Conditioned space (e.g. air/heat) shall be at the discretion of the
owner.
(4) Access to basement shall be by stairway. Trap door access shall not
be permitted.
00082540